18th Edition Test 2

You have 120 minutes (2 hours) to answer 60 18th Edition Questions. You must score at least 36 to pass. You may check answers after each question or wait until the end of the test to view your results. Click the start button to begin. Best of luck!

Tests Taken

Last Score

Average Score

Your Progress

 

Quick view of test questions. Click question box to reveal correct answer.
1. BS 7671 does not apply to Mark one answer
A Mains voltage alarm systems
B Railway signalling equipment
C Site built switchboards
D Site fabricated cable enclosures
Correct Answer: B Railway signalling equipment
Reference: • Amendment 4 (Orange Book) Reference: 110.2(b), page 24 states that railway signalling equipment, including rolling stock and signalling equipment, is excluded from the scope of BS 7671. The other options are covered by BS 7671 where they form part of an electrical installation. Therefore, the correct answer is Railway signalling equipment.
2. Which of the following installations is excluded from the scope of BS 7671? Mark one answer
A A permanent electrical installation in a caravan
B A temporary electrical installation on a construction site
C Equipment of mobile and fixed offshore installations
D Highway power supplies and street furniture
Correct Answer: C Equipment of mobile and fixed offshore installations
Reference: • Amendment 4 (Orange Book) Reference: 110.2(e), page 24 states that equipment of mobile and fixed offshore installations is excluded from the scope of BS 7671. The other options are specifically included within the scope of the Regulations, including construction site installations, highway power supplies and street furniture, and permanent electrical installations in caravans. Therefore, the correct answer is Equipment of mobile and fixed offshore installations.
3. It should be verified that any addition to an existing installation has Mark one answer
A A similar wiring system to that used in the existing installation
B A supply separate from that of the existing installation
C Been treated as being entirely separate from the existing installation
D Not impaired the safety of the existing installation
Correct Answer: D Not impaired the safety of the existing installation
Reference: • Amendment 4 (Orange Book) Reference: Regulation 132.16, page 29, and Regulation 641.5, page 247. Before an addition or alteration is made, it shall be ascertained that the rating and condition of existing equipment are adequate for the altered circumstances and that the necessary earthing and bonding arrangements are suitable. Regulation 641.5 also requires verification that the addition or alteration complies with BS 7671 and does not impair the safety of the existing installation. Therefore, the correct answer is Not impaired the safety of the existing installation.
4. Which one of the following parts of BS 7671 contains greater detail of Selection and Erection of Equipment? Mark one answer
A Part 1
B Part 3
C Part 5
D Part 6
Correct Answer: C Part 5
Reference: • Amendment 4 (Orange Book) Reference: Part 5, Selection and Erection of Equipment, beginning on page 139. Part 5 contains requirements covering common rules for the selection and erection of equipment, wiring systems, protective devices, isolation, switching, control, earthing arrangements and other equipment. Therefore, the correct answer is Part 5.
5. What would an installation with a nominal voltage of 120 V AC between conductors be designated as? Mark one answer
A Extra-low voltage
B Low voltage
C Medium voltage
D Reduced voltage
Correct Answer: B Low voltage
Reference: • Amendment 4 (Orange Book) Reference: Part 2 – Definition: Voltage, nominal, page 50 defines the ranges of nominal voltage as follows: Extra-low voltage: Not exceeding 50 V AC or 120 V ripple-free DC. Low voltage: Exceeding extra-low voltage but not exceeding 1000 V AC or 1500 V DC between conductors. As 120 V AC exceeds the extra-low voltage limit of 50 V AC, it is classified as Low voltage. Therefore, the correct answer is Low voltage.
6. What is the name of the protective conductor that connects exposed-conductive-parts of electrical equipment to the installation's earthing arrangement? Mark one answer
A Bonding conductor
B Circuit protective conductor
C Line conductor
D Protective bonding conductor
Correct Answer: B Circuit protective conductor
Reference: • Amendment 4 (Orange Book) Reference: Figure 2.1, page 51, and Part 2, Terms and Definitions. A circuit protective conductor (CPC) is a protective conductor connecting exposed-conductive-parts of equipment to the installation's earthing arrangement. Circuit protective conductors provide the protective path back towards the main earthing terminal, either directly or through other protective conductor connections. Protective bonding conductors are used to provide protective equipotential bonding. Therefore, the correct answer is Circuit protective conductor.
7. Which of the following supply characteristics would need to be ascertained for an installation? Mark one answer
A Number of points of utilisation
B The external earth fault loop impedance
C The supply cable type
D The supply transformer type
Correct Answer: B The external earth fault loop impedance
Reference: • Amendment 4 (Orange Book) Reference: Regulation 313.1(d), page 62. The characteristics of the electrical supply shall be determined by calculation, measurement, enquiry or inspection. These include the earth fault loop impedance of that part of the system external to the installation, identified as Ze. Therefore, the correct answer is The external earth fault loop impedance.
8. Which of the following is not a characteristic of the supply? Mark one answer
A Emergency switching
B External earth loop impedance Ze
C Frequency
D Nominal voltage
Correct Answer: A Emergency switching
Reference: • Amendment 4 (Orange Book) Reference: Regulation 313.1, page 62. The characteristics of an electrical supply to be determined include nominal voltage and its characteristics, nature of current and frequency, prospective short-circuit current at the origin, external earth fault loop impedance (Ze), suitability for the installation's requirements and the type and rating of overcurrent protective devices at the origin. Emergency switching is not listed as a characteristic of the supply. Therefore, the correct answer is Emergency switching.
9. The earthing arrangement for the system shown is classified as Mark one answer
A TN
B TN-C-S
C TN-S
D TT
Correct Answer: C TN-S
Reference: • Amendment 4 (Orange Book) Reference: Figure 3.8, page 60 identifies the earthing arrangement shown as a TN-S system, where the protective conductor (PE) is provided separately from the neutral conductor throughout the system. Therefore, the correct answer is TN-S.
10. The electrical system in which all exposed-conductive-parts of an installation are connected to an earth electrode, which is electrically independent of the source earth, is Mark one answer
A TN-C
B TN-C-S
C TN-S
D TT
Correct Answer: D TT
Reference: • Amendment 4 (Orange Book) Reference: 312.2.2.1, page 62 states that in a TT system, all exposed-conductive-parts of the installation are connected to an earth electrode that is electrically independent of the source earth. Therefore, the correct answer is TT.
11. Which one of the following ensures safe inspection, testing and maintenance for all installations? Mark one answer
A Division of the installation into circuits
B Protection of the installation by a 30 mA RCD
C Regular calibration of instrumentation
D Regular operational testing of an SPD
Correct Answer: A Division of the installation into circuits
Reference: • Amendment 4 (Orange Book) Reference: 314.1(b), page 63 states that every installation shall be divided into circuits, as necessary, to facilitate safe inspection, testing and maintenance (see also Chapter 46 and Section 537). Therefore, the correct answer is Division of the installation into circuits.
12. Which one of the following should consider measures to reduce the effects of EMI in an installation with regard to electromagnetic compatibility? Mark one answer
A The BSI
B The client or owner
C The designer
D The distributor
Correct Answer: C The designer
Reference: • Amendment 4 (Orange Book) Reference: 332.2, page 64 states that the designer of the electrical installation shall consider the measures necessary to reduce electromagnetic disturbances (EMI) to a level that will not adversely affect electrical equipment or the safe operation of the installation. Therefore, the correct answer is The designer.
13. Where particular risks of fire exist in an area of high density occupation with difficult conditions of evacuation, the external influence code would be Mark one answer
A AD4
B BD3
C BD4
D CA1
Correct Answer: C BD4
Reference: • Amendment 4 (Orange Book) Reference: Appendix 5, Classification of External Influences, page 533. External influence code BD4 identifies locations with high density of occupation and difficult conditions of evacuation. Examples include high-rise buildings open to the public, such as hotels and hospitals. Therefore, the correct answer is BD4.
14. Which of the following is not specifically listed as a potential source of electromagnetic disturbance in Regulation 444.4.1? Mark one answer
A Electric fires
B Electric motors
C Lifts
D Rectifiers
Correct Answer: A Electric fires
Reference: • Amendment 4 (Orange Book) Reference: Regulation 444.4.1, page 118. Potential sources of electromagnetic disturbance within an installation typically include electric motors, rectifiers, lifts, fluorescent lighting, welding machines, choppers, frequency converters, transformers, switchgear and power distribution busbars. Electric fires are not specifically identified in this list, although other equipment may also produce electromagnetic disturbances. Therefore, the correct answer is Electric fires.
15. Where measures are taken against electromagnetic disturbances, what are the minimum nominal dimensions of a flat copper bonding ring network conductor? Mark one answer
A 10mm x 5mm
B 16mm x 8mm
C 25mm x 3mm
D 6mm x 4mm
Correct Answer: C 25mm x 3mm
Reference: • Amendment 4 (Orange Book) Reference: Regulation 444.5.3, page 125. Equipotential bonding designed as a copper bonding ring network shall have minimum nominal dimensions of 25 mm × 3 mm for a flat cross-section conductor or a diameter of 8 mm for a round conductor. Therefore, the correct answer is 25 mm × 3 mm.
16. Which of the following will provide overload protection? Mark one answer
A Circuit-breaker
B Disconnector
C Linked switch
D RCD
Correct Answer: A Circuit-breaker
Reference: • Amendment 4 (Orange Book) Reference: **432.1, page 102** states that a device providing protection against **both overload current and fault current** may be used to protect a circuit. A **circuit-breaker** is specifically intended to provide overload protection, whereas a linked switch, RCD and disconnector do not provide overload protection on their own. Therefore, the correct answer is **Circuit-breaker**.
17. Which of the following is a method of fault protection? Mark one answer
A Insulation of live parts
B Placing out of reach
C Protection by double or reinforced insulation
D Protection by obstacles
Correct Answer: C Protection by double or reinforced insulation
Reference: • Amendment 4 (Orange Book) Reference: 412.1.1, page 82 states that double or reinforced insulation is a protective measure in which basic protection is provided by basic insulation and fault protection is provided by supplementary insulation, or both basic and fault protection are provided by reinforced insulation. Therefore, the correct answer is Protection by double or reinforced insulation.
18. A BS EN 61558-2-5 shaver socket is an example of protection by Mark one answer
A Barriers and enclosures
B Class I equipment
C Electrical separation
D Solid earthing
Correct Answer: C Electrical separation
Reference: • Amendment 4 (Orange Book) Reference: Section 413 states that electrical separation is a protective measure in which a circuit is supplied from a source providing separation from other circuits and from earth, such as a safety isolating transformer. A BS EN 61558-2-5 shaver socket incorporates a shaver supply unit with an isolating transformer to provide protection by electrical separation. Therefore, the correct answer is Electrical separation.
19. If a circuit forming part of a 230 V TT system has an earth fault loop impedance value (Zs) of 500 Ω the rated residual operating current of an RCD would need to be equal to or less than Mark one answer
A 100 mA
B 30 mA
C 300 mA
D 500 mA
Correct Answer: A 100 mA
Reference: • Amendment 4 (Orange Book) Reference: Table 41.5 states that for a TT system, the product of the earth fault loop impedance (Zs) and the rated residual operating current (IΔn) of the RCD must not exceed 50 V (Zs × IΔn ≤ 50). For a circuit with Zs = 500 Ω: 500 × IΔn ≤ 50 IΔn ≤ 0.1 A (100 mA) Therefore, the correct answer is 100 mA.
20. A 32A BS 88-2 fuse is used to protect a distribution circuit. What would the maximum permitted value of earth fault loop impedance (Zs) be? Mark one answer
A 0.91Ω
B 0.99Ω
C 1.6Ω
D 1.7Ω
Correct Answer: D 1.7Ω
Reference: • Amendment 4 (Orange Book) Reference: Table 41.4 gives the maximum permitted earth fault loop impedance (Zs) values for protective devices to achieve the required disconnection time. For a 32 A BS 88-2 fuse, the maximum permitted Zs is 1.7 Ω. Therefore, the correct answer is 1.7 Ω.
21. Which of the following types of fuse system is a BS88-2 fuse? Mark one answer
A B
B C
C D
D E
Correct Answer: D E
Reference: • Amendment 4 (Orange Book) Reference: Table 41.4 identifies the fuse systems recognised for achieving the required disconnection times. A BS 88-2 fuse corresponds to Type B. Therefore, the correct answer is B.
22. When using a non-metallic hand-held piece of equipment, the maximum temperature of any accessible part is Mark one answer
A 30°C
B 45°C
C 55°C
D 65°C
Correct Answer: D 65°C
Reference: • Amendment 4 (Orange Book) Reference: Regulation 423.1 and Table 42.1, page 99. Table 42.1 specifies maximum temperatures under normal load conditions for accessible parts of equipment within arm's reach. For a non-metallic hand-held part, the maximum temperature is 65°C. The corresponding limit for a metallic hand-held part is 55°C. Therefore, the correct answer is 65°C.
23. In a location where a particular risk of fire exists, any temperature cut-out device must Mark one answer
A Be at least IP5X
B Be reset automatically
C Be reset manually only
D Have no reset facility
Correct Answer: C Be reset manually only
Reference: • Amendment 4 (Orange Book) Reference: 422.1.3, page 94 states that in locations where a particular risk of fire exists, temperature cut-out devices provided for protection against excessive temperatures shall only reset manually. This prevents equipment from automatically re-energising after overheating, thereby reducing the risk of ignition. Therefore, the correct answer is Be reset manually only.
24. Which one of the following is a situation where overload protection devices may be omitted for safety reasons? Mark one answer
A The supply circuit of a goods lift
B The supply to a burglar alarm panel
C The supply to a car park barrier
D The supply to a fire alarm
Correct Answer: D The supply to a fire alarm
Reference: • Amendment 4 (Orange Book) Reference: 433.3.3, page 104 states that overload protection devices may be omitted where their operation could create a danger. Examples include circuits supplying rotating machinery, electromagnets, lifting magnets, secondary circuits of current transformers, and safety services. A fire alarm is a safety service, and unwanted operation of an overload protective device could impair its function during an emergency. Therefore, the correct answer is The supply to a fire alarm.
25. What would an overload current result from? Mark one answer
A A disconnected conductor touching an exposed conductive part
B A motor running current exceeding the protective device rating
C Damage to the insulation between live conductors
D Penetration of a cable by a nail
Correct Answer: B A motor running current exceeding the protective device rating
Reference: • Amendment 4 (Orange Book) Reference: **Part 2 (Definitions), page 35** defines an **overload current** as an overcurrent occurring in a circuit that is **not due to a fault**, caused by a load drawing more current than the circuit is intended to carry. A typical example is **a motor running current exceeding the protective device rating**. The other options describe fault conditions that would result in fault current rather than overload current. Therefore, the correct answer is **A motor running current exceeding the protective device rating**.
26. According to Regulation 443.4.1, which of the following is not expressly identified as a consequence requiring protection against transient overvoltages? Mark one answer
A Loss of livestock life
B Serious injury to, or loss of, human life
C Significant data loss
D Significant financial loss
Correct Answer: A Loss of livestock life
Reference: • Amendment 4 (Orange Book) Reference: **443.4, page 115** lists the consequences that shall be considered when determining whether protection against transient overvoltages is required. These include **serious injury to, or loss of, human life**, **interruption of public services**, and **damage to cultural heritage**. **Loss of livestock life** is not one of the specified considerations. Therefore, the correct answer is **Loss of livestock life**.
27. Which one of the following situations is likely to cause severe, temporary overvoltage in an installation? Mark one answer
A Loss of line conductor in a high voltage system
B Loss of line conductor in a low-voltage system
C Loss of neutral conductor in a low voltage system
D Loss of protective conductor in a high voltage system
Correct Answer: C Loss of neutral conductor in a low voltage system
Reference: • Amendment 4 (Orange Book) Reference: **442.1.1 (v), page 111** identifies the **loss of the neutral conductor in a low-voltage system** as a condition that can give rise to severe, temporary overvoltages within an installation. This can result in dangerous overvoltages being applied to equipment connected between line and neutral. Therefore, the correct answer is **Loss of neutral conductor in a low voltage system**.
28. According to Regulation 560.8.1(c), which of the following standards specifies fire-resistance test requirements for certain cables used in safety services required to operate in fire conditions? Mark one answer
A BS 5467
B BS 6231
C BS EN 50200
D IEC 60331-1
Correct Answer: C BS EN 50200
Reference: • Amendment 4 (Orange Book) Reference: Regulation 560.8.1(c), page 240. For safety services required to operate in fire conditions, one recognised wiring system uses fire-resistant cables complying with the test requirements of BS EN 50200, BS 8434 or BS 8491, as appropriate for the cable size, together with BS EN 60332-1-2. Regulation 560.8.1 also recognises other specified fire-resistant wiring systems. Therefore, the correct answer is BS EN 50200.
29. To prevent circulating eddy currents in steel conduit, trunking or cable armouring Mark one answer
A All live conductors of a circuit must be contained in the same enclosure
B Line and neutral conductors are to be kept separate
C Only dc must be used
D The enclosures should be sufficiently earthed
Correct Answer: A All live conductors of a circuit must be contained in the same enclosure
Reference: • Amendment 4 (Orange Book) Reference: Regulation 521.5.1, page 148. Where conductors of an AC circuit are installed in a ferromagnetic enclosure, all line conductors, the neutral conductor where present, and the appropriate protective conductor shall be contained within the same enclosure. This arrangement helps prevent electromagnetic heating effects associated with alternating currents. Therefore, the correct answer is All line conductors, the neutral where present, and the appropriate protective conductor must be contained in the same enclosure.
30. What does a device intended to cut off all voltage from an installation provide? Mark one answer
A Discrimination
B Emergency switching
C Functional switching
D Isolation
Correct Answer: D Isolation
Reference: • Amendment 4 (Orange Book) Reference: **Part 2 (Definitions), page 42* defines **isolation** as a function intended to cut off, for reasons of safety, the supply from all, or a discrete section, of the installation by separating the installation or section from every source of electrical energy. Therefore, the correct answer is **Isolation**.
31. Where the main earth terminal is separate from main switchgear, a permanent label should be fixed in a visible position with the wording Mark one answer
A Danger Earth Connection - Do Not Remove
B Danger Electrical Connection - Do Not Remove
C Safety Earth Connection - Do Not Remove
D Safety Electrical Connection - Do Not Remove
Correct Answer: D Safety Electrical Connection - Do Not Remove
Reference: • Amendment 4 (Orange Book) Reference: **514.13.1, page 145** states that where the main earthing terminal is not adjacent to the main switchgear, a permanent label shall be fixed at or near the main switchgear in a visible position bearing the words **"SAFETY ELECTRICAL CONNECTION – DO NOT REMOVE."** Therefore, the correct answer is **Safety Electrical Connection – Do Not Remove**.
32. A label marked with the words ‘Safety Electrical Connection - Do Not Remove’ must be fixed at or near the Mark one answer
A Connection to each earth electrode
B Control gear for discharge lighting
C Final circuit fuse
D Supply of the fire alarm circuits
Correct Answer: A Connection to each earth electrode
Reference: • Amendment 4 (Orange Book) Reference: **514.13.1 (i), page 145** states that a label bearing the words **"SAFETY ELECTRICAL CONNECTION – DO NOT REMOVE"** shall be permanently fixed at or near **the connection to each earth electrode**. This identifies the earthing connection and warns against its removal. Therefore, the correct answer is **Connection to each earth electrode**.
33. A non-flame-propagating conduit, cable trunking or cable ducting system has a maximum internal cross-sectional area of 710 mm². If the IP33 requirements of Regulation 527.2.3 are satisfied, which of the following applies when it penetrates building construction? Mark one answer
A Must be internally sealed
B Must be internally sealed if passing through a brick wall
C Need not be internally sealed
D Need only be sealed if passing through an insulating partition
Correct Answer: C Need not be internally sealed
Reference: • Amendment 4 (Orange Book) Reference: Regulation 527.2.3, page 159. A conduit, cable trunking or cable ducting system classified as non-flame propagating and having a maximum internal cross-sectional area of 710 mm² need not be internally sealed where it penetrates building construction, provided the system satisfies IP33 and any termination in the relevant compartment also satisfies IP33, in accordance with BS EN 60529. Therefore, the correct answer is Need not be internally sealed.
34. To what depth should cables that are placed directly in the ground be buried at? Mark one answer
A They should be buried not less than 0.75 m
B They should be buried not less than 1.5 m
C They should be buried sufficiently to allow easy access
D They should be buried sufficiently to avoid damage
Correct Answer: D They should be buried sufficiently to avoid damage
Reference: • Amendment 4 (Orange Book) Reference: **522.8.10, page 152** states that cables installed directly in the ground shall be buried at a sufficient depth to avoid being damaged by any reasonably foreseeable disturbance of the ground. No specific minimum burial depth is prescribed in BS 7671. Therefore, the correct answer is **They should be buried sufficiently to avoid damage**.
35. What rating factor applies to a cable with conductor cross-sectional area not exceeding 10 mm², totally surrounded by thermal insulation for a length of 200 mm, under the conditions specified in Appendix 4? Mark one answer
A 0.51
B 0.63
C 0.78
D 0.88
Correct Answer: B 0.63
Reference: • Amendment 4 (Orange Book) Reference: Appendix 4, Section 2.6, page 451. For a cable totally surrounded by thermal insulation over a length of 200 mm, a rating factor of 0.63 applies under the specified conditions for conductor sizes not exceeding 10 mm² and insulation thermal conductivity greater than 0.04 W/(m·K). Therefore, the correct answer is 0.63.
36. Which of the following types of SPD are most suitable for installation at the origin of the supply to protect against overvoltage? Mark one answer
A Type0
B Type1
C Type3
D Type4
Correct Answer: B Type1
Reference: • Amendment 4 (Orange Book) Reference: Regulation 534.4.1.1(a), page 173. SPDs installed at the origin of an electrical installation shall be Type 1 or Type 2. Type 1 SPDs are particularly suitable where protection against lightning-related surge currents is required, including installations where lightning protection considerations require a Type 1 SPD. Therefore, the correct answer is Type 1.
37. Which one of the following can be used as a device for emergency switching? Mark one answer
A 20 A plug and socket-outlet
B Semiconductor devices
C Switched fused connection unit
D Unswitched fused connection unit
Correct Answer: C Switched fused connection unit
Reference: • Amendment 4 (Orange Book) Reference: **Table 537.4, page 193** identifies the devices that may be used for emergency switching. A **switched fused connection unit** is permitted for this purpose, provided it complies with the relevant requirements. Semiconductor devices alone are not acceptable for isolation or switching, an unswitched fused connection unit cannot perform a switching function, and a 20 A plug and socket-outlet is not recognised for emergency switching. Therefore, the correct answer is **Switched fused connection unit**.
38. Where practical, the main protective equipotential bonding to the gas services in a building should be made within Mark one answer
A 3m of the meter on the consumer’s side
B 3m of the meter on the supply side
C 600mm of the meter on the consumer’s side
D 600mm of the meter on the supply side
Correct Answer: C 600mm of the meter on the consumer’s side
Reference: • Amendment 4 (Orange Book) Reference: 544.1.2, page 216 states that, where practical, the main protective equipotential bonding connection to a gas installation shall be made as near as practicable to the point of entry of the service into the premises and **within 600 mm of the gas meter outlet (consumer's side)** before any branch pipework. Therefore, the correct answer is **600 mm of the meter on the consumer’s side**.
39. The minimum CSA of a supplementary bonding conductor not protected against mechanical damage and run as a separate cable should be Mark one answer
A 1.5 mm2
B 2.5 mm2
C 4.0 mm2
D 6.0 mm2
Correct Answer: C 4.0 mm2
Reference: • Amendment 4 (Orange Book) Reference: 544.2.1, page 216 states that where a supplementary protective bonding conductor is not incorporated in the same wiring system as the live conductors and is not provided with mechanical protection, it shall have a minimum cross-sectional area of 4.0 mm² copper. Therefore, the correct answer is 4.0 mm2.
40. A firefighter's switch should comply with which of the following requirements? Mark one answer
A It musn't be more than 3.75m from the ground
B It must be electrically linked
C It must be in a locked location to prevent nuisance operation
D It should be at the main entrance to the building
Correct Answer: D It should be at the main entrance to the building
Reference: • Amendment 4 (Orange Book) Reference: 537.4.2.2 (ii), page 197 states that a firefighter's switch shall be positioned so that it is readily accessible to firefighters, typically at the main entrance to the building. The switch is required to be mounted not more than **2.75 m** above ground level, so the 3.75 m option is incorrect. Therefore, the correct answer is **It should be at the main entrance to the building**.
41. A source for a safety service should be supplied from a Mark one answer
A Capacitor
B DC motor
C Generator set
D Rectifier
Correct Answer: C Generator set
Reference: • Amendment 4 (Orange Book) Reference: 560.6.1, page 238 states that a source for a safety service shall be supplied from a source independent of the normal supply. A generator set is specifically identified as a suitable independent source for safety services. Therefore, the correct answer is Generator set.
42. What is the name of the document that must be issued following the periodic inspection and testing of an electrical installation? Mark one answer
A Electrical Installation Certificate
B Electrical Installation Condition Report
C Minor Electrical Installation Works Certificate
D Periodic Inspection Report
Correct Answer: B Electrical Installation Condition Report
Reference: • Amendment 4 (Orange Book) Reference: 653.1, page 255 states that following the periodic inspection and testing of an existing electrical installation, an Electrical Installation Condition Report (EICR), based on the model given in Appendix 6, shall be issued. Therefore, the correct answer is Electrical Installation Condition Report.
43. The test voltage to be used for an insulation resistance test between the lines of a 400 V three-phase circuit is Mark one answer
A 1000Vdc
B 250Vdc
C 500Vdc
D 750Vdc
Correct Answer: C 500Vdc
Reference: • Amendment 4 (Orange Book) Reference: Regulation 643.3.2 and Table 64, page 249
Table 64 specifies a test voltage of 500 V DC for circuits with a nominal voltage above 50 V up to and including 500 V. Therefore, the correct answer is 500 V DC.
44. By whom should an Electrical Installation Certificate be signed by? Mark one answer
A An electrician
B One or more skilled persons competent to verify compliance with BS 7671
C The designer of the installation only
D The person ordering the inspection
Correct Answer: B One or more skilled persons competent to verify compliance with BS 7671
Reference: • Amendment 4 (Orange Book) Reference: Regulations 644.4 and 644.5, page 253. The person or persons responsible for the design, construction and verification of an electrical installation shall issue the appropriate certificate, taking account of their respective responsibilities. Electrical Installation Certificates shall be compiled and signed or otherwise authenticated by one or more skilled persons competent to verify that the requirements of BS 7671 have been met. Therefore, the correct answer is One or more skilled persons competent to verify compliance with BS 7671.
45. Which of the following tests is not included in the prescribed pre-energisation test sequence specified by Regulation 643.1 for tests under Regulations 643.2 to 643.6? Mark one answer
A Continuity of conductors
B Earth fault loop impedance
C Insulation resistance
D Protection by SELV
Correct Answer: B Earth fault loop impedance
Reference: • Amendment 4 (Orange Book) Reference: Regulation 643.1, page 248. The relevant tests specified in Regulations 643.2 to 643.6 shall be carried out in the stated order before the installation is energized. Earth fault loop impedance testing is covered by Regulation 643.7.3 and is not included in that prescribed sequence. Where an installation incorporates an earth electrode, the test under Regulation 643.7.2 shall also be carried out before energization. Therefore, the correct answer is Earth fault loop impedance.
46. What is the general minimum degree of protection required for electrical equipment installed in Zones 1 and 2 of a bathroom, excluding specified shaver supply units and equipment exposed to water jets? Mark one answer
A IP2X
B IP4X
C IPX2
D IPX4
Correct Answer: D IPX4
Reference: • Amendment 4 (Orange Book) Reference: Regulation 701.512.2, page 259. Electrical equipment installed in Zones 1 and 2 of a location containing a bath or shower shall generally have a degree of protection of at least IPX4. Equipment exposed to water jets shall have at least IPX5. An exception applies to certain shaver supply units complying with BS EN 61558-2-5 installed in Zone 2 where direct shower spray is unlikely. Therefore, the correct answer is IPX4.
47. What is the general minimum degree of protection required for electrical equipment installed in a hot-air sauna where cleaning by water jets is not expected? Mark one answer
A IP22
B IP3X
C IP4X
D IPX4
Correct Answer: D IPX4
Reference: • Amendment 4 (Orange Book) Reference: Regulation 703.512.2, page 272. Electrical equipment installed in a sauna shall have a degree of protection of at least IPX4. Where cleaning by water jets may reasonably be expected, the required minimum degree of protection increases to IPX5. Therefore, under normal conditions without water-jet cleaning, the correct answer is IPX4.
48. Within Zones 0 and 1 of a swimming pool, a protective provision against electric shock should be by means of Mark one answer
A SELV
B non-conducting location
C obstacles
D placing out of reach
Correct Answer: A SELV
Reference: • Amendment 4 (Orange Book) Reference: Regulation 702.410.3.4.1, page 263. In swimming pools, protection by SELV is permitted in Zone 0 at a nominal voltage not exceeding 12 V AC RMS or 30 V ripple-free DC, and in Zone 1 at a nominal voltage not exceeding 25 V AC RMS or 60 V ripple-free DC. The SELV source shall generally be installed outside Zones 0, 1 and 2, subject to the specific provisions of the regulation. Therefore, the correct answer is SELV.
49. Which one of the following is not classified as an outdoor lighting installation? Mark one answer
A A luminaire on an outside wall of a building, internally fed
B An illuminated road sign
C The illumination for an outdoor monument
D The lighting arrangement for an advertising panel
Correct Answer: A A luminaire on an outside wall of a building, internally fed
Reference: • Amendment 4 (Orange Book) Reference: Regulation 714.1, page 325
Luminaires fixed to the outside of a building and supplied directly from the internal wiring of that building are excluded from the classification of outdoor lighting installations. Therefore, this is the correct answer.
50. Which protective measure is permitted for independent electrical switches installed in Zone 1 of a location containing a bath or shower, subject to the voltage and safety-source requirements of Regulation 701.512.3? Mark one answer
A Non-conducting location
B PELV
C Placing out of reach
D SELV
Correct Answer: D SELV
Reference: • Amendment 4 (Orange Book) Reference: Regulation 701.512.3, page 259
In zone 1, only switches for SELV circuits not exceeding 12 V AC or 30 V ripple-free DC may be installed, with the safety source outside zones 0, 1 and 2. Therefore, the correct answer is SELV.
51. According to Regulation 714.512.2.105, what is the specified minimum IP degree of protection for electrical equipment in outdoor lighting installations? Mark one answer
A IP22
B IP24
C IP33
D IP44
Correct Answer: C IP33
Reference: • Amendment 4 (Orange Book) Reference: Regulation 714.512.2.105, page 326
Electrical equipment in outdoor lighting installations shall have, by construction or installation, a degree of protection of at least IP33. Therefore, the correct answer is IP33.
52. In a bathroom, the protective measure of obstacles is Mark one answer
A Allowed in all zones
B Allowed in zone 2 only
C Allowed in zones 1 and 2
D Not allowed
Correct Answer: D Not allowed
Reference: • Amendment 4 (Orange Book) Reference: Regulation 701.410.3.5, page 258
The protective measures of obstacles and placing out of reach shall not be used in locations containing a bath or shower. Therefore, the correct answer is Not allowed.
53. According to Regulation 709.512.2.1.4, what minimum IK impact protection rating may be used for electrical equipment installed on a pontoon in a marina where mechanical impact of medium severity (AG2) is anticipated? Mark one answer
A IK08
B IP55
C IPX4
D IPX8
Correct Answer: A IK08
Reference: • Amendment 4 (Orange Book) Reference: Regulation 709.512.2.1.4, page 288. Electrical equipment installed on or above a jetty, wharf, pier or pontoon shall be protected against mechanical damage of medium severity (AG2). One permitted method is to install equipment complying with a minimum degree of protection against external mechanical impact of IK08. Other permitted methods include suitable positioning and local or general mechanical protection. Therefore, the correct answer is IK08.
54. What minimum classification of mechanical protection should electrical equipment in zones 0 and 1 of a fountain have? Mark one answer
A AG0
B AG1
C AG2
D AG3
Correct Answer: C AG2
Reference: • Amendment 4 (Orange Book) Reference: Regulation 702.55.3, page 266
Electrical equipment in zones 0 and 1 of fountains shall have mechanical protection to medium severity, classified as AG2. Therefore, the correct answer is AG2.
55. What is the minimum height above ground for overhead insulated conductors installed in areas subject to vehicle movement at marinas and similar locations? Mark one answer
A 3.0m
B 3.5m
C 5.8m
D 6.0m
Correct Answer: D 6.0m
Reference: • Amendment 4 (Orange Book) Reference: Regulation 709.521.1.8, page 289. In marinas and similar locations, overhead conductors shall be insulated and installed at a height of not less than 6 m above ground in areas subject to vehicle movement, and not less than 3.5 m in other areas. Therefore, the correct answer is 6.0 m.
56. Which one of the following is the correct grouping factor for six circuits bunched on a surface? Mark one answer
A 0.45
B 0.55
C 0.57
D 0.69
Correct Answer: C 0.57
Reference: • Amendment 4 (Orange Book) Reference: Appendix 4, Table 4C1, page 471. Item 1 of Table 4C1 specifies a grouping factor of 0.57 for six circuits bunched in air, on a surface, embedded or enclosed, with the cables touching. The factor applies to uniform groups of equally loaded cables. Therefore, the correct answer is 0.57.
57. An external influence has a general category code of B. What does this code indicate? Mark one answer
A Capability
B Environment
C Temperature
D Utilisation
Correct Answer: D Utilisation
Reference: • Amendment 4 (Orange Book) Reference: Appendix 5, page 520
Appendix 5 states that the first letter B in an external-influence code represents the general category of utilisation. Therefore, the correct answer is Utilisation.
58. A circuit is protected by a 20 A BS 3036 semi-enclosed fuse. What is the minimum permissible current rating (Iz) of a conductor protected by this fuse? Mark one answer
A 20.0 A
B 27.6 A
C 29.4 A
D 36.0 A
Correct Answer: B 27.6 A
Reference: • Amendment 4 (Orange Book) Reference: Regulations 433.1.1 and 433.1.202, page 103
For a BS 3036 fuse, Regulation 433.1.202 requires the conductor current-carrying capacity to be divided by the correction factor 0.725. Therefore, Iz must be at least 20 ÷ 0.725 = 27.6 A.
59. Equipment is being installed that must be capable of being immersed in water and must withstand a temperature range of -5℃ to +40℃. What are the classification categories of external influences for this equipment? Mark one answer
A AA4 and AF3
B AA6 and AD5
C AD7 and AA4
D AK2 and AD7
Correct Answer: C AD7 and AA4
Reference: • Amendment 4 (Orange Book) Reference: Appendix 5, pages 520 and 525
Appendix 5 classifies AA4 as an ambient temperature range of −5 °C to +40 °C and AD7 as equipment subject to immersion in water. Therefore, the correct classifications are AD7 and AA4.
60. Where can details on current-carrying capacity and voltage drop for busbar trunking and powertrack systems be found? Mark one answer
A Appendix 12
B Appendix 14
C Appendix 15
D Appendix 8
Correct Answer: D Appendix 8
Reference: • Amendment 4 (Orange Book) Reference: Appendix 8, page 562
Appendix 8 contains the requirements and guidance for the current-carrying capacity and voltage drop of busbar trunking and powertrack systems. Therefore, the correct answer is Appendix 8.